Energy-optimized control of HVAC systems with recirculation and heat recovery in cleanrooms
author:
MONIKA JAKUBIAK, MIECZYSŁAW POROWSKI
ORCID ID:
0000-0001-8176-2952, 000- 0002-9793-6133
No:
7-8/2021 Instal p. 20-24
DOI:
DOI 10.36119/15.2021.7-8.3
The article presents algorithms of energy-optimal control of a standard HVAC system with recirculation, heat
recovery (rotary energy regenerator) and a dry cooler in a recirculation cycle for a cleanroom ISO5 (M3.5, cl.
100). The annual demand for usable, final and primary energy was determined for thermodynamic air treatment
and the case of real loads and operating parameters, as well as two control variants: standard – variant I and
energy-optimal – variant II. A simulation model of the HVAC system operation throughout the year was formulated
as an analysis tool. It has been shown that the implementation of energy-optimal control algorithms (variant II)
allows to reduce the annual primary energy demand of the HVAC system by as much as 39.2% compared to the
standard strategy (variant I).