Proposal of diagnostic method for distribution network
author:
DARIUSZ KOWALSKI, BEATA KOWALSKA, PAWEŁ SUCHORAB
ORCID ID:
0000-0001-9929-1626, 0000-0003- 2489-1904, 0000-0001-9275-4800
No:
7-8/2021 Instal s.55-60
DOI:
10.36119/15.2021.7-8.8
The aim of this paper is to present the detecting abnormal conditions system, including its concepts and effects after
3-month period operation. The analysed water supply system, of total pipe length equal to approx. 260 km, consists of 24 pressure zones, 7 water tanks and 15 water pumping stations. The essence of the system is the integration of
numerical model (developed in Bentley WaterGems software) and SCADA monitoring system. The monitoring data
are constantly compared to simulation results and when accepted compliance limits are exceeded the appropriate
alerts are generated. Such solution cause that the WSS operator does not need to analyse SCADA system
indications constantly. The additional application of the system enables the detection of water leakages.