Visualisation method for assessment of frost formation on air cooler
author:
PAWEŁ JAKOŃCZUK, JERZY GAGAN, KAMIL ŚMIERCIEW, DARIUSZ BUTRYMOWICZ
ORCID ID:
000-0002-7607-9654, 0000-0003-3869-8347
No:
5/2020 instal p. 11-16
DOI:
10.36119/15.2020.5.2
Finned tube heat exchangers are widely used in heating, ventilation, air conditioning and refrigeration. In the case
of exchangers operating as air coolers, frost formation occurs, which generally strongly deteriorates the efficiency of
heat transfer by creating additional thermal resistance and causing additional pressure loss. The paper provides with
the analysis of the effect of frosting process on the operation of the air cooler using the method proposed by the
authors using observations synchronised with thermal measurements of air cooler. On the basis of long-term tests of
the air cooler operating in the vegetables cold storage chamber the influence of frosting process was assessed,
among others on cooling capacity, bypass factor, and thermal resistance. In the analysed case, frosting reduced the
cooling capacity by up to 40%.