The problem of integrating control systems for thermally activated building slabs and ventilation in educational buildings
author:
KATARZYNA PAŁASZYŃSKA, KAROL BANDURSKI, MIECZYSŁAW POROWSKI
ORCID ID:
0000-0002-3403-7536, 0000-0001-8578-7233
No:
03/2024 Instal pp.31-38
DOI:
10.36119/15.2024.3.4
In the article, the issue of control HVAC (Heating, Ventilation, Air Conditioning) systems with thermally activated building systems (TABS) in educational buildings, characterized by large and dynamically changing internal cooling loads, is presented. The problem of dissipating cooling loads through the TABS system in this kind of building was identified. The use of ventilation air to dissipate a portion of these loads was proposed, and simple control algorithms integrating the TABS system and the air system were compared. A simulation model of the system’s operation throughout the year was developed using the TRNSYS17 program as a research tool.
The optimization problem of selecting energy-optimal control was solved, where the constraints were to meet thermal comfort conditions (operative temperature within the required range), and the objective function was to minimize the primary energy demand of the HVAC system throughout the year. TABS system control algorithms were based on: heating and cooling curves determined with the Unknown-But-Bounded (UBB) method and switching temperatures were determined with an original author’s method.
Calculations were carried out for a case study – a lecture room in an educational building. It was demonstrated that only the integration of the TABS system with ventilation, also acting to dissipate part of the thermal loads TABS+VAV (Variable Air Volume), allows maintaining the operative temperature within the required comfort range for 83% of the occupation time for the most favorable comfort control variant. In the case where ventilation only served hygiene purposes – TABS+DCV (Demand Control Ventilation), the time of operative temperature within the comfort range was only 14% of the room’s occupation time for the most favorable control variant.
Keywords:
About Authors:
mgr inż. Katarzyna Pałaszyńska https://orcid.org/0000-0002-3403-7536, dr inż. Karol Bandurski https://orcid.org/0000-0001-8578-7233, dr hab. inż. Mieczysław Porowski, prof. PP https://orcid.org/0000-0002-9793-6133 ‒ Instytut Inżynierii Środowiska, Wydział Inżynierii Środowiska i Energetyki, Politechnika Poznańska
Corresponding author: katarzyna.palaszynska@put.poznan.pl